On November 26, 2026, The Register published Dan Olds' SC26 column "45°C inlets just killed the chiller. Most people haven't noticed yet", which reached the Hacker News front page. Its claim: "Jump to 45°C (113°F) and a whole bunch of datacenters that currently need chillers suddenly don't." Chillers, it says, "are thankfully unnecessary now for new datacenter builds."
What the primary sources say
- NVIDIA. Its June 21 blog post says Rubin servers can run cooling liquid "up to 45 degrees Celsius" and that the generation is "100% liquid cooling" with "no fans anywhere in the system." Its cooling director, Ali Heydari, qualifies it: a dry-cooler design is closed-loop "outside of maybe 1% of the year when we might need chillers in some climates."
- A cooling vendor. CoolIT's January 20 response is titled "The Future Is Here but It's Not Chiller-Free." It argues warm-water cooling "is not new" and that "ASHRAE standards have supported elevated water temperatures since 2011."
- The column's own numbers. Olds cites "published estimates and vendor modeling" of a 50 to 70 percent cut in cooling energy and a 10 to 20 percent drop in total facility power. Those are modelled ranges, not measurements from a named site.
The debate
Both sides agree on the physics: if chips accept 45 C coolant, dry coolers on the roof can reject heat for most hours in most places without refrigeration. They disagree on what "most" means for a design. A facility must meet its worst hour, not its average one. In a hot climate, or during a heatwave, the approach temperature of a dry cooler can push supply above 45 C, and the choices then are a trim chiller, adiabatic assist that uses water, or throttled GPUs. Retrofit is the other limit: the column itself notes that existing pipes, pumps and heat exchangers were sized for colder loops.
Analysis: for AI workloads the question translates into a scheduling one. If a site has no chiller, its capacity during the hottest hours depends on how much the cluster can throttle, so training jobs need checkpoint cadence and serving needs headroom elsewhere. "Chiller-optional" is a reasonable design target for new builds in temperate climates. It is not a property of the chip alone.
Original exercise, not executed: Geetha asks a hosting provider for the Belgavi's Book Store model cluster three numbers: the site's design wet-bulb and dry-bulb temperatures, the coolant supply temperature at the 99.6th percentile hour, and what happens to GPU clocks if supply exceeds the rated inlet. A provider that can answer all three has actually designed for the edge case.
What to watch
Whether AMD and Intel publish matching inlet ratings, and the first measured annual PUE and water figures from a chiller-free AI site.
Sources accessed November 27, 2026. Views are my own and do not represent any employer, past or present.
I think the column is right about the direction and too quick about the conclusion. NVIDIA's own engineer says "maybe 1% of the year" and "some climates," and that 1% is exactly the hour a capacity plan must survive. What has changed is that the chiller moves from the main plant to a backup role, sized for peaks. That is a big saving. It is not the same as deleting it, and I would want measured numbers from a real site before treating it as settled.
Sources and evidence
- The Register: 45°C inlets just killed the chiller. Most people haven't noticed yet (November 26, 2026)
- NVIDIA Blog: Hotter Than a Hot Tub: The 45°C Breakthrough to Cool AI's Biggest Machines (June 21, 2026)
- CoolIT Systems: Warm Water Cooling and AI: The Future Is Here but It's Not Chiller-Free (January 20, 2026)
- Hacker News discussion (November 26, 2026)
NVIDIA rates Rubin for 45 C liquid inlets and says chillers may still be needed about 1% of the year in some climates. A Register SC26 column says chillers are now unnecessary for new builds, and a cooling vendor disagrees. Design for the hottest hour: chillers become peak backup, not gone.